ICG Heat Pumps

ICG Heat Pumps 🔥Low Carbon Heating Solutions🔥

01/02/2026
01/02/2026

We always recommend that our clients specify separate systems to do DHW and space heating. ✅

Experience has shown us that having one system to do both, results in neither being done very well

Heat pumps serving heating systems should always be looking to reduce flow temperature based on the internal and external temperature to maximise efficiency

Stored hot water should be maintained at 60degrees and so requires a flow temperature of around 65degrees ♨️

Using one system to do both will mean that the system has to ramp up from the weather compensated temperature to 65degrees every time water is drawn off making the systems inefficient

If it doesn't ramp up when water is drawn off the DHW temperature drops below 60 and you risk low DHW temperatures ❌

Because we have always run boilers at high temp, we have always used the same boiler to do both and have carried this mentality forward

Do this with a heat pump and the result
is high running costs 💷💷💷

Yes, you have to buy 2 heat pumps, but you probably have to buy a bigger one and also have to spend money on extra hydraulics , 3 port valve and BMS controls

In many applications the DHW load is very small

On this project, we supplied a
midea MARS heat pump

This model gives 35KW with 65/55 flow and return temperatures (-5 ambient)

It cost about the same as the extra cost of making the heat pump bigger and the required components and controls

This will be cheaper to run than standalone system

The unit also uses propane refrigerant making it future proof