Breakdown investigation at Discobowl in Newport shopping centre. System not cooling at all. Found condenser fan speed co...
01/06/2026

Breakdown investigation at Discobowl in Newport shopping centre. System not cooling at all. Found condenser fan speed controller faulty with unit cycling on high pressure safety switch. Temporarily by passed to keep plant operating. New fan speed controller required

Saturday trip down to Labyrinth night club in Barnstable. Water leak from failed condensate tank pump. New pump fitted a...
01/06/2026

Saturday trip down to Labyrinth night club in Barnstable. Water leak from failed condensate tank pump. New pump fitted and all Air conditioning serviced. Cellar cooling short of gas, high pressure leak test required.

Fault investigation work carried out on this Mitsubishi Electric VRV system after site power issues. All reset and now f...
01/06/2026

Fault investigation work carried out on this Mitsubishi Electric VRV system after site power issues. All reset and now fully operational

Breakdown visit to a pub restaurant kitchen in Gloucestershire with a Foster Blast chiller running warm. Evaporator coil...
21/05/2026

Breakdown visit to a pub restaurant kitchen in Gloucestershire with a Foster Blast chiller running warm. Evaporator coil end plates had corroded away causing rust to pierce the refrigerant copper tubes. Due to the age and condition of the cabinet, advised customer to replace rather than waste money on repair

The need for planned preventative maintenance should be seriously considered. Not just for plant efficiency but also for...
21/05/2026

The need for planned preventative maintenance should be seriously considered. Not just for plant efficiency but also for health as well. This cellar cooling system was thoroughly stripped and chemically cleaned

Site visit to Worcester Bosch yesterday for Neptunes to investigate reported under performing extract flow issues in R&D...
21/05/2026

Site visit to Worcester Bosch yesterday for Neptunes to investigate reported under performing extract flow issues in R&D and Hydrogen testing labs. Whilst on site found chilled water up to over +20c with water chillers held off. Found Grundfos circulation pump in fault. Further work required

Repairs carried out on these Daikin VRV slave condensing units at Cotswold BMW Cheltenham. Faulty Inverter compressors a...
21/05/2026

Repairs carried out on these Daikin VRV slave condensing units at Cotswold BMW Cheltenham. Faulty Inverter compressors and Inverter PCB's changed. System now fully operational for the hot weather we get (hopefully)

Recent breakdown visit to Trilogy nightclub in Blackpool for Aircool Technology. Found various Panasonic units with faul...
21/05/2026

Recent breakdown visit to Trilogy nightclub in Blackpool for Aircool Technology. Found various Panasonic units with faults and units under performing due to vast amounts of confetti

Recent relocation work carried out at a nightclub in Durham for Aircool Technologys
21/05/2026

Recent relocation work carried out at a nightclub in Durham for Aircool Technologys

Service work carried out today at Dr Fosters on cellar cooling, Ice maker and main kitchen coldroom ready for the warm w...
07/05/2026

Service work carried out today at Dr Fosters on cellar cooling, Ice maker and main kitchen coldroom ready for the warm weather.