Oil boiler attended last week that was filling the room with carbon monoxide, apparently this boiler was service yearly ๐ณ the customer had just moved in and 1st time using the boiler the room filled with co setting alarms off.
The flue seals were leaking and not even connected inside the boiler, combustion products leaking from both upper and lower burner doors, baffles where seized in place and completely full with soot, couldnโt get any air flow through the heat exchanger, the poor thing was in a real sorry state.
The old flue was removed and replaced with a plume, the boiler was stripped bare, cleaned and cleared of soot to within and inch of its life, took about 3 hours just to get the baffles out. Door rope seals replaced.
The boiler is now running perfectly with perfect readings ๐