Empire Leak Detection

Call Directions Website Contact the business

Empire Leak Detection Finding leaks requires cutting edge sophisticated equipment. Our locating techniques are non-invasive

09/17/2026

Two birds with one stone.

Slabzzzz 💧
09/17/2026

Slabzzzz 💧

Large gas leak at a Sacramento school renovation. The contractor isolated a leaking 200’ section of poly, and tracer gas...
08/20/2026

Large gas leak at a Sacramento school renovation. The contractor isolated a leaking 200’ section of poly, and tracer gas testing produced two elevated H₂ readings about 20’ apart. The first location turned out to be the end of a 4” PVC conduit that the poly gas line ran through, explaining why tracer gas was surfacing away from the actual leak. Excavation at the second location exposed the source: a leaking coupling just before the poly entered the conduit. An excavator had struck the line, gouging a chunk out of both the fitting and the pipe. A good example of how tracer gas can travel through conduit and create readings well away from the actual failure.

No way to electronically trace the pipe on this one, but the peak acoustic readings lined up with the presumed path of t...
08/20/2026

No way to electronically trace the pipe on this one, but the peak acoustic readings lined up with the presumed path of the main. We narrowed the leak down to a 10’ x 10’ section of slab and drilled pressure-relief holes along the suspected path. Even at low pressure, the entire slab was loud no matter which acoustic device I used. Drilling pressure-relief holes and probing down closer to the pipe helped eliminate trapped and traveling compressed gas, allowing me to narrow the leak back down to my original marked location. 🤣

2000’ 10” fire suppression loop leaking approximately 250k gallons an hour. Massive 14’ crack!! Peak readings and a soun...
08/16/2026

2000’ 10” fire suppression loop leaking approximately 250k gallons an hour. Massive 14’ crack!! Peak readings and a sound like I have never heard before on the digital, it cut out the volume on my analog it was so loud!

Nighttime Commercial Leak Detection at Kaiser
03/03/2026

Nighttime Commercial Leak Detection at Kaiser

02/06/2026

Early morning commercial leak detection at Costco 🎯

01/20/2026

Commercial 2” water service under red clay up in the hills.. Again, tracer gas got me in the vicinity but nailed it acoustically. Soil conditions don’t always allow for the tracer gas to surface above the leak.

PGE shut off gas to residence. Filled her up with tracer gas. Ends up being the last place I looked 🤣 Confirmed with soa...
01/19/2026

PGE shut off gas to residence. Filled her up with tracer gas. Ends up being the last place I looked 🤣 Confirmed with soap test so the customer could see.

Commercial underground leak. Tracer gas got me in the vicinity, ended up switching to acoustic to pinpoint. The actual l...
01/19/2026

Commercial underground leak. Tracer gas got me in the vicinity, ended up switching to acoustic to pinpoint. The actual leak was 20 feet away from where the Tracer gas was surfacing that’s why it’s important to confirm your Tracer gas findings with acoustic.

Address

8863 Greenback Lane #298
Orangevale, CA
95662

Opening Hours

Monday 8am - 4pm
Tuesday 8am - 4pm
Wednesday 8am - 4pm
Thursday 8am - 4pm
Friday 8am - 4pm

Telephone

+19165450825

Alerts

Be the first to know and let us send you an email when Empire Leak Detection posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to Empire Leak Detection:

Shortcuts

Share