New York Electrical Inspection Agency

New York Electrical Inspection Agency We believe electrical inspections should educate, not overwhelm. Professional Electrical Inspections

Our team is committed to safety, clear communication, modern technology, and exceptional service, helping homeowners and contractors stay compliant and protected.

06/01/2026

Missing weather cover on an exterior receptacle.

Exterior receptacles are exposed to rain, snow, sprinklers, condensation, and moisture. That’s why the 2023 NEC requires receptacles installed in wet locations to have a weatherproof cover that protects the receptacle whether or not a cord is plugged in.

📖 2023 NEC 406.9(B)(1) requires receptacles in wet locations to have an enclosure that is weatherproof when an attachment plug is inserted.

A missing cover may seem minor, but moisture and electricity are never a good combination.

❓Would you pass this inspection, or require correction before approval?

05/29/2026

⚡️Would You Pass This? ⚡️

Take a look at this electrical panel. The panel itself may be installed correctly, but what about the table and sink located in front of it?

🤔 Does this setup provide the required working space for safe access, operation, and maintenance?

The 2023 NEC requires electrical equipment to have sufficient working clearance under NEC 110.26. The purpose isn’t just to open the panel door—it’s to provide a safe workspace for anyone who may need to inspect, troubleshoot, or service the equipment.

📏 Is the required depth and width of working space being maintained?
🚫 Can furniture or fixtures occupy that space?
✅ Or is this installation acceptable?

What would your decision be as an inspector, electrician, or homeowner?

PASS ✅ or FAIL ❌?

Drop your answer and reasoning in the comments. 👇

05/28/2026

Hydromassage bathtub fail 🚫🛁⚡

The motor cord was run through the wall and plugged into a receptacle in the closet of the adjacent room… and the receptacle wasn’t even GFCI protected.

2023 NEC 680.73 requires hydromassage bathtub electrical equipment to be accessible without damaging the building finish. If the tub is cord-and-plug connected through an access panel, the receptacle must be within direct view and within 1 foot of the opening.

Can’t run a cord through the wall to another room.

And the receptacle isn’t even GFCI protected.

What do you think:
⚠️ Shortcut install?
⚠️ Didn’t know the code?
⚠️ Or “it passed before” syndrome?

Drop your thoughts below 👇

05/27/2026

FAIL ❌

2023 NEC Article 230.85(A)(1) requires the emergency disconnect for a one- or two-family dwelling to be installed in a readily accessible outdoor location.

This disconnect was installed in the basement — not outside.

The purpose of the emergency disconnect is to allow first responders and occupants to quickly shut off power without entering the building during an emergency.

Outside means outside. Not in the basement.

05/23/2026

💡 What’s wrong with this picture?

This exterior light fixture has a couple of problems.

First, the fixture base appears to be buried behind the siding, leaving only the bulb exposed. The electrical box and wiring connections must remain accessible and cannot be concealed behind the finished surface. If you have to remove siding to access the box, it’s not accessible.

📖 2023 NEC 314.29 requires boxes to be installed so the contained wiring can be rendered accessible. Boxes recessed into or behind finished surfaces must have access maintained through an opening in the cover and building finish.

Second, this appears to be an indoor-rated fixture installed outdoors. Fixtures installed in wet or damp locations must be listed for the environment where they are installed.

📖 2023 NEC 410.10(A) requires luminaires installed in wet locations to be listed for wet locations, and those installed in damp locations to be listed for damp or wet locations.

🔍 Question: Would you pass this installation, or write it up?

05/20/2026

NM cable inside conduit?
Yes — that can be allowed.

But here’s the catch 👇

If that conduit is installed in a wet location, the inside of the conduit is considered a wet location too under 2023 NEC 300.9. That means standard NM cable (Romex) is no longer permitted because 2023 NEC 334.12 prohibits NM cable in wet or damp locations.

So while conduit can protect NM cable in some dry locations, outdoor, underground, or wet-location conduit changes everything.

⚡ Dry location = possibly acceptable
💧 Wet location = code violation


Know the difference before you pull wire.

05/19/2026

Can NM cable (Romex) be run outside and overhead to a detached garage? 🤔

Short answer: No.

According to the 2023 NEC, standard NM cable is not permitted in wet or damp locations — and the outside of a building is considered a wet location, even under an overhang. That means running exposed Romex overhead outdoors to a garage is a code violation.

Outdoor wiring methods typically require conductors and raceways listed for wet locations.

05/18/2026

What do you think…
are they already living here before it’s finished? 👀🏠⚡️

No drywall. Exposed framing. Wires everywhere.
But somehow… the furniture’s already moved in.

Be honest, would you stay here?

05/17/2026

Built-in bookshelves may look great… until they block access to the electrical panel. ⚡📚

2023 NEC Article 110.26 requires working clearance in front of electrical equipment. That means no permanent shelving, storage, or obstructions in the required workspace.

Electrical panels need safe access for operation, maintenance, and emergencies — not a wall of books.

📏 Minimum working depth often required: 3 feet
🚫 No storage in the dedicated workspace
⚠️ Safety and accessibility matter

05/17/2026

“Can you really put a receptacle anywhere? 🤔

What about between two doors? 🚪⚡🚪

According to the NEC, receptacle placement rules are more specific than many people realize. Door swings, wall space measurements, and usable wall area all matter when determining if an outlet is required — or even practical.

Would this location count as required wall space in your opinion?

Address

2767 Dewey Avenue
Rochester, NY
14616

Alerts

Be the first to know and let us send you an email when New York Electrical Inspection Agency posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to New York Electrical Inspection Agency:

Share